magistrsko delo
Valentina Markovič (Avtor), Rok Fink (Recenzent), Martina Oder (Mentor)

Povzetek

Uvod: Bakterije iz rodu Legionella so povzročiteljice legionarske bolezni in pontiaške vročice. Tveganje za okužbo je povsod, kjer nastanejo aerosoli. Do povečanega števila bakterij prihaja v notranjem okolju zgradb (vodovod, prezračevalne naprave, bazeni itd.), kjer je temperatura vode v omrežju med 20 in 50 °C. Slepi vod je izraz za vodovodne cevi in pipe, ki niso ali so redko v uporabi, oz. za dele cevi, ki so zaradi renoviranja postale nepretočne. Namen: Želeli smo ugotoviti intenzivnost razmnoževanja bakterij iz rodu Legionella v slepih vodih in manj pretočnih mestih. Metode dela: V raziskavi smo izdelali sistem, s katerim smo simulirali delovanje vodovodnega sistema v zgradbi. Sistem je imel vgrajene tri različne slepe vode. Predhodno smo opravili preliminarne poskuse in tako preverili razmnoževanje bakterije Legionella pneumophila v različnih medijih. Izbrani medij smo uporabili za nadaljnje raziskave, s katerimi smo napolnili simulator vodovodnega sistema. Intenzivnost razmnoževanja bakterij smo preverili v sistemu in slepih vodih po 24 urah, 72 urah in po 120 urah delovanja sistema. Rezultati: Po 24 urah inkubacije v simulatorju vodovodnega sistema je bilo število bakterij najmanjše v slepem vodu 3 (3,656 log CFU ml-1), v sistemu, kjer je voda krožila in ostalih slepih vodih pa približno enako (približno 4,5 log CFU ml-1). Po 72 urah inkubacije je bilo najvišje število bakterij v sistemu, kjer je voda krožila (6,523 log CFU ml-1). V slepem vodu 3 je bilo najmanjše število bakterij (6,131 log CFU ml-1). Po 120 urah inkubacije je bilo najmanjše število bakterij v slepem vodu 3 (3,970 log CFU ml-1), najvišje pa v slepem vodu 2 (4,464 log CFU ml-1). Razprava in zaključek: Ugotovili smo, da so se bakterije Legionella intenzivno razmnoževale po celotnem vodovodnem sistemu, najmanj v slepem vodu 3. Naši rezultati so pokazali minimalne razlike med številom bakterij ne glede na obliko in dolžino slepega voda; slepi vod ne vpliva na intenziteto razmnoževanja bakterij. Smiselno bi bilo nadaljevati raziskavo, da se podaljša čas izpostavljenost bakterij v vodovodnem sistemu. Predpostavljamo, da bi se šele po daljši izpostavljenosti lahko pokazale morebitne večje razlike pri razmnoževanju bakterij Legionella, ki so v vodovodnem sistemu in slepih vodih.

Ključne besede

magistrska dela;sanitarno inženirstvo;pneumophila;slepi vodi;legioneloza;okužbe;vodovodni sistem;

Podatki

Jezik: Slovenski jezik
Leto izida:
Tipologija: 2.09 - Magistrsko delo
Organizacija: UL ZF - Zdravstvena fakulteta
Založnik: [V. Markovič]
UDK: 614
COBISS: 14502915 Povezava se bo odprla v novem oknu
Št. ogledov: 710
Št. prenosov: 191
Ocena: 0 (0 glasov)
Metapodatki: JSON JSON-RDF JSON-LD TURTLE N-TRIPLES XML RDFA MICRODATA DC-XML DC-RDF RDF

Ostali podatki

Sekundarni jezik: Angleški jezik
Sekundarni naslov: Reproduction of bacteria Legionella pneumophila in dead legs of the water system
Sekundarni povzetek: Introduction: Bacteria of the genus Legionella are the disease agent of the Legionnaires' disease and the Pontiac fever. The risk for the infection is everywhere where the aerosols emerge. An increased number of bacteria emerges in the internal environment of buildings (water distribution system, ventilation devices, swimming pools, etc.) where the temperature of the water in the system is between 20 and 50 °C. A dead leg is an expression for water pipes that are not or are rarely in use and for the parts of water pipes which became non-flow pipes because of the renovation. Purpose: We wished to ascertain the intensity of bacterial growth of the genus Legionella in dead legs and the positions with less water flow. Methods: In the research, we produced a system by which we simulated the working of the water distribution system in the building. Three different dead legs were built in the system. We performed preliminary experiments and, thus, we checked the reproduction of the Legionella pneumophila bacteria in different media. We used the selected media for further research by which we filled a simulator of the water distribution system. We checked the intensity of the bacteria reproduction in the system and dead legs after 24 hours, 72 hours, and 120 hours of the working of the system. Results: After 24 hours of incubation in the simulator of the water distribution system, the number of bacteria was the smallest in the dead leg 3 (3.656 log CFU ml-1). In the system where water was circulating and in the remaining dead legs, the number of bacteria was approximately the same (approximately 4.5 log CFU ml-1). After 72 hours of incubation, the highest number of bacteria was in the system where water was circulating (6.523 log CFU ml-1). In the dead leg 3, there was the smallest number of bacteria (6.131 log CFU ml-1). After 120 hours of incubation, the smallest number of bacteria was in the dead leg 3 (3.970 log CFU ml-1) and the highest was in the dead leg 2 (4.464 log CFU ml-1). Discussion and conclusion: We ascertained that the bacteria Legionella were reproducing intensively in the entire water distribution system, least in the dead leg 3. Our results showed minimal differences in the number of bacteria regardless of the shape and length of a dead leg. A dead leg does not influence the intensity of the reproduction of the bacteria in the water distribution system. It would make sense to continue the research in a sense to prolong the time of exposure of the bacteria in the water distribution system. We assume that only after more time of exposure, differences in the reproduction of the Legionella bacteria, which are in the water distribution system and in dead legs, could emerge.
Sekundarne ključne besede: master's theses;sanitary engineering;Legionella pneumophila;dead legs;legionelosis;infection;water system;
Vrsta dela (COBISS): Magistrsko delo/naloga
Študijski program: 0
Konec prepovedi (OpenAIRE): 1970-01-01
Komentar na gradivo: Univ. v Ljubljani, Zdravstvena fak., Oddelek za sanitarno inženirstvo
Strani: 47 str.
ID: 11648570